| |
|
Falcon Fire Sprinkler Company performs
periodical inspection services on all wet fire protection systems.
Inspections are
conducted in accordance with NFPA 25 standards, including full testing of
systems and devices to ensure that all components are in prime working
condition. We offer inspection programs geared to provide automatic
periodic inspections required by NFPA 25 and the authority having jurisdiction.
Wet fire sprinkler inspections are required on a
monthly, quarterly, annually, and five-year basis. Click the link below to download the NFPA regulations for
the inspection, testing, and maintenance of water-based fire sprinkler
systems.
Download NFPA Regulations [PDF]
In accordance to NFPA 25 regulations, the following periodic procedures are
performed by Falcon Fire Sprinkler Company when the wet system is
inspected.
MONTHLY
- Inspect all gauges to ensure they are in
good working condition and normal water supply pressure is being
maintained. If the gauges are not working properly or are more than
five years old, they are replaced.
- Inspect all control valves to ensure they are:
- in the proper open or closed position
- properly sealed, locked or supervised
- accessible
- provided with appropriate wrenches
- free of external leaks
- free of external corrosion
provided with appropriate
identification
If the wet fire sprinkler has an alarm
valve, the exterior body is inspected to ensure:
- the gauges indicate normal supply pressure
- valve is free of physical damage
- the proper open or closed position
- in the proper open or closed position
there is no leakage from the retarding chamber
or alarm drains
QUARTERLY
- Inspect alarm devices to verify they are
free of physical damage.
- Inspect hydraulic nameplate to verify that it is
attached securely to the riser and legible.
- Inspect pressure regulating control valves to
verify they are:
- in the open position
- not leaking
- maintaining downstream pressure in accordance
to design criteria
- in good working condition with hand wheels
installed and unbroken.
- Main drain test at each system riser to determine if there has been a change in
the condition of water supply piping and control valves.
- Water flow test is conducted by
opening the inspector's test connection.
- Fire department connections are
inspected to verify the following:
- connections are visible and accessible
- couplings or swivels are not damaged and rotate
smoothly
- plugs or caps are in place and undamaged
- gaskets are in place and in good condition
- identification signs are in place
- the check valve is not leaking
- the automatic drain valve is in place and
operating properly.
ANNUALLY
- Inspect all gauges to ensure they are in
good working condition and normal water supply pressure is being
maintained. If the gauges are not working properly or are more than
five years old, they are replaced.
- All sprinkler heads are inspected to verify
they are free of corrosion, foreign materials, paint, and physical damage.
They are also checked to make sure they are installed in the proper
orientation.
- Piping and fittings are inspected to ensure
they are in good condition and free of mechanical damage, leakage,
corrosion, and misalignment. Sprinkler piping is inspected to make
sure they are not subject to external loads.
- Hangers and seismic bracing are inspected to
verify they are in good condition.
- The spare
head box is inspected that it contains the following: the proper number
and type of sprinklers present on the premises, and a sprinkler wrench for
each type of sprinkler head.
- Every control valve is operated through its full
range and returned to its normal position. They are lubricated if
necessary.
- A flow test is conducted on each riser and
compared to previous test results if available.
- The antifreeze loop solution is tested.
- Obstruction investigation where maintenance or
repair requires the replacement of sprinkler system components affecting
more than twenty sprinklers.
FIVE-YEAR
INSPECTION AND TESTING
- Gauges are tested and/or replaced.
- Extra high temperature sprinklers (> 325 degrees)
are replaced.
- Internal inspection of alarm valve.
Automatic fire sprinkler systems have demonstrated to provide
the best protection against loss of life and property in the event of a
fire. They protect
from the onset of a fire, by responding to heat. In the case of a wet
automatic fire sprinkler system, water spray from the sprinkler immediately
starts to control the fire. At the same time, as the water flows
through the system, an alarm activates to alert the building occupants and
the fire department (if monitored). There has never been a multiple
loss of life from fire in a fully sprinkled building.
The authority having jurisdiction (local Fire
Marshal) may at sometime request a copy of your fire sprinkler inspection
report or reports. If you cannot find the copy we gave you upon completion
of our inspection, you may retrieve it on-line. As an added benefit
being our customer, you have access to view or print the completed
inspection report or reports forty-eight hours after Falcon Fire Sprinkler
has performed the service. The documents are protected by encrypted
username and password protection.
FYI about automatic wet fire sprinkler suppression
systems, go
here. To discuss
residential or business sprinkler system inspections with one of our
representatives, call (816) 734-0018, or contact us
on-line. Licensed
• Insured • Professional

|
|
Website
maintained by Dr. William D. Ramey, editor
Copyright © 1996 - 2006 William Ramey
Internet
Address
All Rights Reserved
|
|